Observation: Differential pressure rising; SAT drifting high in Zone 4.
Reason: Filter loading pattern matches prior failure precursor.
Constraint: No autonomous damper override in occupied mode without approval.
Action: Recommend filter WO + SAT trim pending approval
Expected: Comfort index recovery in Zone 4.
Actual: Awaiting approval
Confidence: 88%
Rollback: N/A — recommend mode
2026-11-18T08:15:00Z · Approve Before Action — Airside
When outside wet-bulb is between 68–74°F, occupancy exceeds 3,200, and Chiller 2 condenser approach rises beyond 3.2°F, this plant historically requires a 0.5–0.8°F CW target adjustment.
AHU-12 filter DP events preceded Zone 4 comfort complaints by 6–9 hours across the last three cooling seasons.