Equipment

AHU-12

Asset ID: eq-ahu12

sat
55.1°F
damper
42%
filter
Dirty
AI Confidence
88%

Explainable AI

Observation: Differential pressure rising; SAT drifting high in Zone 4.

Reason: Filter loading pattern matches prior failure precursor.

Constraint: No autonomous damper override in occupied mode without approval.

Action: Recommend filter WO + SAT trim pending approval

Expected: Comfort index recovery in Zone 4.

Actual: Awaiting approval

Confidence: 88%

Rollback: N/A — recommend mode

2026-11-18T08:15:00Z · Approve Before Action — Airside

Ciright Brain memory

When outside wet-bulb is between 68–74°F, occupancy exceeds 3,200, and Chiller 2 condenser approach rises beyond 3.2°F, this plant historically requires a 0.5–0.8°F CW target adjustment.

AHU-12 filter DP events preceded Zone 4 comfort complaints by 6–9 hours across the last three cooling seasons.

Lifetime timeline

2019
Installed
2020
Compressor replacement
2021
Efficiency baseline
2022
Control sequence changed
2023
VFD installed
2024
Major service
2026
SCADA AI connected
2027
Ciright Glass activated

Authority mode

Monitor OnlyRecommendApprove Before ActionBounded AutonomousFully Autonomous Within PolicyEmergency HoldManual Override