Chiller 03

Asset ID: eq-ch03

load
72%
efficiency
0.54 kW/ton
chws
44.2°F
chwr
55.6°F
approach
2.8°F
AI Confidence
96%

Explainable AI

Observation: Condenser-water temperature increasing under rising wet-bulb.

Reason: Opportunity to lower cooling-tower fan energy while maintaining chiller constraints.

Constraint: Maintain CHWS within 44.0–44.5°F and compressor envelope.

Action: CW target adjusted −0.5°F

Expected: Plant kW reduced without comfort impact.

Actual: Plant kW reduced 2.1%.

Confidence: 94%

Rollback: Revert CW target if approach > 3.5°F for 10 minutes.

2026-11-18T09:42:00Z · Bounded Autonomous — Chiller Plant Policy v3

Ciright Brain memory

When outside wet-bulb is between 68–74°F, occupancy exceeds 3,200, and Chiller 2 condenser approach rises beyond 3.2°F, this plant historically requires a 0.5–0.8°F CW target adjustment.