Equipment
Asset ID: eq-ch03
Observation: Condenser-water temperature increasing under rising wet-bulb.
Reason: Opportunity to lower cooling-tower fan energy while maintaining chiller constraints.
Constraint: Maintain CHWS within 44.0–44.5°F and compressor envelope.
Action: CW target adjusted −0.5°F
Expected: Plant kW reduced without comfort impact.
Actual: Plant kW reduced 2.1%.
Confidence: 94%
Rollback: Revert CW target if approach > 3.5°F for 10 minutes.
2026-11-18T09:42:00Z · Bounded Autonomous — Chiller Plant Policy v3
When outside wet-bulb is between 68–74°F, occupancy exceeds 3,200, and Chiller 2 condenser approach rises beyond 3.2°F, this plant historically requires a 0.5–0.8°F CW target adjustment.
AHU-12 filter DP events preceded Zone 4 comfort complaints by 6–9 hours across the last three cooling seasons.