Equipment
Asset ID: eq-ct01
No autonomous actions on this asset in the current demo window.
When outside wet-bulb is between 68–74°F, occupancy exceeds 3,200, and Chiller 2 condenser approach rises beyond 3.2°F, this plant historically requires a 0.5–0.8°F CW target adjustment.
AHU-12 filter DP events preceded Zone 4 comfort complaints by 6–9 hours across the last three cooling seasons.